摘 要:简介四喷嘴对置式气化炉烧嘴冷却水泵回路配置及联锁设置的情况,针对运行过程中出现的诸多问题,分析其原因,并采取了一系列优化、改造措施,由此保障了气化炉的长周期稳定运行。
关键词:气化炉;烧嘴冷却水泵;回路配置;联锁设置;问题分析;改造
中图分类号:TQ545 文献标志码:B 文章编号:1003-6490(2014)06-0059-05
Revamp of the Gasifier Burner Cooling Water Pump Circuit and It's Interlock Optimization
YAN Jing-luan
[New Energy Phoenix(Tengzhou) Energy Co.,Ltd.,Tengzhou Shandong 277527,China]
Abstract: Describe the cooling water pump circuit configuration of opposed four-nozzles gasifier and it's interlock set. To solve many problems in the operation,analyze the causes and take a series of optimization,revamp measures. Thus long-term stable operation of the gasifier is guaranteed.
Key words:gasifier; burner cooling water pump; circuit configuration; interlock set;analyze problem; revamp
德士古工艺烧嘴是气化装置的关键设备,一般为三流道外混式设计,在烧嘴中煤浆被高速氧气流充分雾化,以利于气化反应。德士古烧嘴插入气化炉燃烧室中,我公司正常生产状况下,烧嘴承受1350 ℃左右的高温;为防止烧嘴损坏,在烧嘴外侧设置冷却盘管,在烧嘴头部设置水夹套,并由2台烧嘴冷却水泵、冷却水槽、事故烧嘴水泵向烧嘴供应冷却水,同时,系统设置了复杂的安全联锁。由于烧嘴冷却水泵的电气回路配置容量偏小,元器件选用国产,联锁系统不完善,曾因长期高负荷运行和电气产品的性能下降,出现电器元件发热、设备回路误动的问题,渐渐不能满足烧嘴冷却水泵长期满负荷运行的需要。
1 烧嘴冷却水泵回路及联锁简介
1.1 烧嘴冷却水系统
公司设有P1201A/B 2台烧嘴冷却水泵,型号 TSP100-150-340L,流量 144 m3/h,扬程 280 m;电机型号 YB315L-2,功率185 kW,转速 2970 r/min。由烧嘴冷却水泵加压,冷却水经烧嘴冷却水换热器冷却后送入4个工艺烧嘴的冷却水盘管内,最后采用低进高出的形式进入烧嘴头部的水夹套对其进行强制冷却,从而达到保护烧嘴的目的。P1204事故烧嘴冷却水泵1台,型号 TSP50-100-340L,流量 72 m3/h,扬程 280 m;电机型号 YB315M-2,功率 132 kW,转速 2970 r/min;在2台烧嘴冷却水泵出现故障时使用。
目前,公司共有3台1500 t/d气化炉,每台气化炉采用四喷嘴对置式设置,正常生产状况为2台气化炉105%负荷运行、1台气化炉备用,日....